Electrical Unit Conversions
Electrical unit conversion reference
Some conversions are fixed scale changes: 1 kW equals 1,000 W regardless of the circuit. Others require a physical relationship. Watts cannot be converted to amps without voltage and, for AC real power, power factor and circuit configuration. Likewise, Wh and mAh require the associated nominal voltage. Use the following tables as mathematical examples, not equipment ratings.
kVA to amps quick reference
Each cell gives single-phase / balanced three-phase RMS current in amperes at the listed RMS voltage (line-to-line for three-phase). The formulas are 1,000 × kVA / V and 1,000 × kVA / (√3 × V), respectively.
| kVA | 120 V (1φ / 3φ) | 240 V (1φ / 3φ) | 400 V (1φ / 3φ) | 480 V (1φ / 3φ) |
|---|---|---|---|---|
| 1 | 8.33 / 4.81 | 4.17 / 2.41 | 2.50 / 1.44 | 2.08 / 1.20 |
| 5 | 41.67 / 24.06 | 20.83 / 12.03 | 12.50 / 7.22 | 10.42 / 6.01 |
| 10 | 83.33 / 48.11 | 41.67 / 24.06 | 25.00 / 14.43 | 20.83 / 12.03 |
| 15 | 125.00 / 72.17 | 62.50 / 36.08 | 37.50 / 21.65 | 31.25 / 18.04 |
mAh to Wh at different nominal voltages
| mAh | 3.7 V | 5 V | 12 V | 24 V |
|---|---|---|---|---|
| 1000 | 3.70 | 5.00 | 12.00 | 24.00 |
| 5000 | 18.50 | 25.00 | 60.00 | 120.00 |
| 10000 | 37.00 | 50.00 | 120.00 | 240.00 |
| 20000 | 74.00 | 100.00 | 240.00 | 480.00 |
Values are in Wh. Multiply mAh by nominal voltage and divide by 1,000. For the reverse conversion, divide Wh by nominal voltage and multiply by 1,000. This is nominal stored energy, not guaranteed delivered energy.
Watts, kilowatts and mechanical horsepower
| W | kW | Mechanical hp |
|---|---|---|
| 100 | 0.1 | 0.134 |
| 500 | 0.5 | 0.671 |
| 1000 | 1 | 1.341 |
| 1500 | 1.5 | 2.012 |
| 2000 | 2 | 2.682 |
| 5000 | 5 | 6.705 |
One mechanical horsepower is approximately 745.6999 W. Horsepower has other definitions; this table uses the mechanical definition. A motor's shaft output cannot be used as electrical input without efficiency information. Source: NIST conversion factors.
Power and current converters
Watts to Amps — real power and voltage to current; AC requires power factor.
Amps to Watts — measured current and voltage to real power; AC requires power factor.
Watts to Volts — real power divided by current, including AC factors.
Volts to Watts — voltage multiplied by current, including AC factors.
kVA to Amps — apparent power and voltage to RMS current.
kVA to kW — multiply apparent power by power factor.
Amps to kW — current and voltage to real power in kilowatts.
kW to Amps — convert real power in kilowatts to current.
Amps to kVA — RMS voltage and current to apparent power.
kW to kVA — divide real power by positive power factor.
Volts to Amps — voltage plus real power or known ideal DC resistance.
HP to Amps — mechanical horsepower, efficiency and supply parameters to an estimated current.
Charge and energy converters
mAh to Wh — charge capacity and nominal voltage to stored energy.
Wh to mAh — energy and nominal voltage to equivalent charge.
Watts to kWh — constant or average watts and operating time to energy.
For model derivations and variable definitions, see electrical formulas. For circuit calculations beyond conversion, visit the calculator directory.