Electrical Formulas
1. Ohm’s law: voltage, current and resistance
For an ideal linear resistor, V = I × R. V is potential difference in volts, I is current in amperes, and R is resistance in ohms. Rearranging gives I = V / R and R = V / I, provided the denominator is positive.
Example: 0.02 A through an ideal 150 Ω resistor corresponds to 3 V. If a problem specifies milliamperes, divide that value by 1,000 before entering it in amperes. For a resistance expressed in kilohms, multiply by 1,000. Use the Ohm’s law calculator to solve the missing quantity.
2. DC and single-phase real power
For a DC operating point, P = V × I, where P is real power in watts. For an ideal linear DC resistor, substitution gives P = I² × R or P = V² / R for positive R. Example: 12 V and 2 A gives 24 W. At 6 Ω the equivalent resistive-power equations give the same result.
For single-phase AC, P = V × I × PF, where V and I are RMS quantities and PF is real power divided by apparent power. Example: 120 V, 5 A and PF 0.8 give 480 W. For an inverse calculation, I = P / (V × PF), which requires positive voltage and PF. Use volts to watts or watts to amps.
3. Balanced three-phase power
For a balanced three-phase AC load, P = √3 × VLL × I × PF. VLL denotes line-to-line RMS voltage, I line current, and P total real electrical input across the phases. Apparent power S = √3 × VLL × I is expressed in VA.
Example: 400 V line-to-line, 10 A and PF 0.8 give approximately 5,542.56 W, or 5.543 kW. Apparent power is about 6.928 kVA. If a stated power is in kW, multiply by 1,000 before using a watt-based formula. The model does not apply unchanged to unbalanced loads. See kW to amps and kVA to amps.
4. Apparent power and power factor
PF = P / S, with real and apparent power expressed in compatible units, such as kW and kVA. Thus P = S × PF. Example: an illustrative 10 kVA load at PF 0.8 has 8 kW of real power. With 8 kW and 10 kVA measured at the same operating point, PF = 0.8.
For a nonnegative load model the ratio ranges from zero to one. Zero apparent power does not identify a finite ratio. PF is not efficiency; efficiency compares useful output power with input power. Use kVA to kW or the power factor calculator.
5. Voltage drop
For a DC two-conductor circuit with equal outgoing and return resistances, ΔV = 2 × I × L × R. Here L is one-way length in kilometers and R is resistance per conductor in Ω/km. Example: 5 A, 10 m and 5 Ω/km give 0.5 V. Percentage drop = 100 × ΔV / supply voltage, so at 24 V this is approximately 2.083%.
For sinusoidal AC with lagging displacement power factor, the approximate longitudinal drop uses R × PF + X × √(1 − PF²), where X is inductive reactance per kilometer. Multiply this term by 2 × I × L for single-phase, or √3 × I × L for balanced three-phase. For example, single-phase 10 A, 0.02 km, R = 4, X = 0.2 and PF = 0.8 gives 1.328 V. These are hypothetical inputs, not installation specifications. See the voltage drop calculator.
6. Energy, charge and battery estimates
For average real power P in watts and duration t in hours, E = P × t / 1,000 in kWh. Multiply by the number of identical devices if their schedules match. Example: three hypothetical 60 W devices running for five hours use 0.9 kWh. Use kWh calculator.
Nominal energy in Wh is approximately Ah × nominal voltage, so Wh = mAh × V / 1,000. Example: 10,000 mAh at 3.7 V represents approximately 37 Wh. Use mAh to Wh or Wh to mAh.
For average load power P, nominal stored energy E in Wh, usable fraction u and conversion efficiency η, ideal estimated battery runtime is t = E × u × η / P. Example: 500 Wh, u = 0.9, η = 0.85, P = 60 W gives 6.375 hours. Reverse the expression to estimate nominal capacity: E = P × t / (u × η). See battery runtime and battery capacity. Manufacturer ratings and discharge conditions take precedence.
7. Energy cost
For a constant average load in watts, daily energy = P × hours per day / 1,000. The energy charge for n days equals daily energy × n × rate in dollars per kWh. Example: 1,500 W for two hours daily at a hypothetical $0.16/kWh gives $0.48 per day and $14.40 over 30 days. Fixed fees and other tariff components are excluded. See electricity cost calculator.
8. Resistor networks
For positive parallel resistance values, equivalent resistance is 1 / (1/R1 + 1/R2 + …). Two 100 Ω branches yield 50 Ω. For a two-resistor unloaded voltage divider, Vout = Vin × R2 / (R1 + R2). A hypothetical 12 V input and equal resistors give 6 V. A finite load in parallel with R2 changes the output. See parallel resistor and voltage divider.
References and scope
Consult OpenStax University Physics, NIST SI guide and the calculation methodology. These equations describe ideal or approximate mathematical models, not wiring instructions or installation approval.