kVA to Amps Calculator

Convert apparent power in kVA to amps for single-phase or balanced three-phase AC. Enter RMS voltage to calculate current and see worked examples.

CALCULATOR WORKSPACE Live calculation
Calculated current—

Formula and units

Single-phase: I = 1000 × S / V. Balanced three-phase: I = 1000 × S / (√3 × VLL), where S is in kVA.

Use RMS voltage and current for AC. Three-phase equations assume a balanced load and line-to-line voltage. Power factor is not needed for apparent power. Do not substitute kW for kVA without accounting for power factor.

Worked examples

A 5 kVA single-phase supply at 230 V corresponds to 21.74 A. A balanced 15 kVA three-phase supply at 400 V corresponds to 21.65 A.

How to interpret the result

The output is current in amperes, not energy consumption or an equipment rating. Input values are treated as steady-state quantities. For changing loads, use an appropriate measurement or estimate rather than assuming a single operating value covers all conditions. Display rounding does not increase measurement accuracy.

Related calculations

Watts to amps · Ohm’s law · Electrical formulas · Conversions

This is an educational calculation, not an installation approval. See our methodology.

Apparent power ratings versus real power

A label expressed in kVA already represents apparent power; do not multiply by power factor before calculating RMS current. For example, a balanced 12 kVA three-phase load at 400 V line-to-line corresponds to approximately 17.32 A. Its real power would be 9.6 kW if PF were 0.8, but the apparent-power-to-current calculation is unchanged.

If you know the real power instead, use kW to amps. To compare the two ratings, use kVA to kW. These conversions do not establish an allowable operating current, equipment selection or wiring requirement.

Reference: Fluke, balanced three-phase AC power.

Current reference by apparent power and voltage

The table compares single-phase RMS current and balanced three-phase line current. All three-phase columns use line-to-line voltage. Apparent power is the total kVA for the circuit in the applicable model.

Apparent power 120 V 1-phase 240 V 1-phase 400 V 3-phase 480 V 3-phase
0.5 kVA 4.1667 A 2.0833 A 0.72169 A 0.60141 A
1 kVA 8.3333 A 4.1667 A 1.4434 A 1.2028 A
2 kVA 16.667 A 8.3333 A 2.8868 A 2.4056 A
3 kVA 25 A 12.5 A 4.3301 A 3.6084 A
5 kVA 41.667 A 20.833 A 7.2169 A 6.0141 A
7.5 kVA 62.5 A 31.25 A 10.825 A 9.0211 A
10 kVA 83.333 A 41.667 A 14.434 A 12.028 A
15 kVA 125 A 62.5 A 21.651 A 18.042 A
20 kVA 166.67 A 83.333 A 28.868 A 24.056 A
25 kVA 208.33 A 104.17 A 36.084 A 30.07 A
30 kVA 250 A 125 A 43.301 A 36.084 A
50 kVA 416.67 A 208.33 A 72.169 A 60.141 A

For example, 10 kVA at 240 V single-phase corresponds to about 41.67 A, while 10 kVA at 400 V balanced three-phase corresponds to approximately 14.43 A. These examples are mathematical comparisons, not equipment capacity or allowable-current recommendations.

Why power factor does not appear in the equation

The input is apparent power rather than real power. Single-phase apparent power equals RMS voltage times RMS current. In the balanced three-phase model it equals √3 times line-to-line RMS voltage times line current. The current calculation rearranges those relationships.

If the source value is 10 kW of real electrical input rather than 10 kVA, the problem is different. At PF 0.8, 10 kW corresponds to 12.5 kVA. Substituting 10 directly into a kVA field would underestimate the calculated current for that operating point. Use kW to kVA first or calculate current directly with kW to amps.

Identify the supply and units

A single-phase 240 V calculation does not include a square-root-of-three factor merely because the voltage number is high. The factor comes from the balanced three-phase relationship, not the voltage magnitude itself. For three-phase, the voltage input is line-to-line, not phase-to-neutral. The calculator does not infer the supply configuration from the entered voltage.

If apparent power is given in VA, divide it by 1,000 before entering kVA. For an illustrative 750 VA single-phase operating point at 120 V RMS, enter 0.75 kVA. The calculated current is 6.25 A.

Reverse-check the current

To verify arithmetic, convert the output current back to kVA using the same voltage and phase model with amps to kVA. A balanced three-phase 400 V example with about 14.4338 A returns about 10 kVA. Rounding the displayed current may introduce a small numerical difference.

A transformer or generator label may state a rated apparent power rather than actual measured load. This tool calculates the corresponding mathematical current at the stated voltage; it does not establish a permissible loading schedule or equipment selection. Actual conditions, phase imbalance, thermal limits and protection requirements need independent assessment.

Avoid invalid assumptions

The entered voltage must be positive because it is a denominator. A zero apparent-power input with positive voltage gives zero current under the simplified model. The tool does not model unbalanced phases, current harmonics in detail, fault currents or startup conditions. See electrical formulas and DC vs AC for the underlying relationships.

Frequently asked questions

What information does this calculation require?

Power factor is not needed for apparent power. Do not substitute kW for kVA without accounting for power factor.

Can I use the result to choose a breaker?

No. Protective equipment selection requires additional installation and equipment information and applicable standards.