Electrical Units and Reference Charts

Electrical units and symbols

Use this reference to identify the quantity before choosing a calculator. Unit symbols distinguish power from energy and charge from current. In SI notation, a space separates the numerical value and symbol, and capitalization matters.

Quantity Unit Symbol Meaning
Voltage volt V potential difference
Current ampere A charge per second
Resistance ohm Ω volt per ampere
Real power watt W joule per second
Energy joule J watt-second
Charge coulomb C ampere-second
Frequency hertz Hz cycles per second
Apparent power volt-ampere VA RMS voltage-current product
Energy kilowatt-hour kWh 3.6 million joules
Charge capacity ampere-hour Ah 3,600 coulombs

SI prefixes

Prefix Symbol Multiplier
mega M 1,000,000
kilo k 1,000
milli m 0.001
micro µ 0.000001

For example, 2.2 kΩ equals 2,200 Ω, while 15 mA equals 0.015 A. The symbol mW means milliwatts; MW means megawatts. They differ by a factor of one billion. A kilowatt-hour is an energy quantity, not kilowatts per hour. The NIST SI guide is a reference for notation and units.

Power unit equivalences

Quantity Equivalent watts
1 kW 1,000
1 mechanical hp 745.6999
1 Btu IT/h 0.2930711
1 ton of refrigeration 3,516.853

A ton of refrigeration describes a heat-transfer rate, not the electrical power consumed by an air conditioner. Mechanical horsepower describes a power rate and can refer to output rather than electrical input. The conversions use the definitions in NIST conversion factors. Do not confuse the efficiency of equipment with a fixed unit conversion.

Apparent power and real power

kVA kW at PF 0.8 kW at PF 0.9 kW at PF 1
1 0.80 0.90 1
5 4.00 4.50 5
10 8.00 9.00 10
15 12.00 13.50 15
20 16.00 18.00 20

The table uses P = S × PF with consistent kilo-units. Power factor is the ratio of real power to apparent power under the stated operating conditions; it is not conversion efficiency. Use the power factor calculator when both quantities are known. The current required for a stated real power also depends on voltage and supply configuration.

Current at common voltages

This table is for single-phase AC at unity power factor or the corresponding DC equation, not a rating table. It assumes constant real electrical input power. The balanced three-phase result at a specified line-to-line voltage is different.

Real power (kW) 120 V (A) 240 V (A) 480 V (A)
1 8.33 4.17 2.08
2 16.67 8.33 4.17
5 41.67 20.83 10.42
10 83.33 41.67 20.83
15 125.00 62.50 31.25
20 166.67 83.33 41.67

For a single-phase example at 0.8 power factor, divide the unity-PF current by 0.8. For balanced three-phase, use total real power and line-to-line RMS voltage with the square-root-of-three factor. See kW to amps. The table does not determine the safe current of an installation.

Conductor dimensions and AWG

American Wire Gauge describes nominal round conductor size. Lower gauge numbers correspond to larger nominal diameters. The AWG chart provides diameter in inches and millimeters and circular cross-sectional area in square millimeters, including 1/0 through 4/0. It describes geometry, not the outer diameter of insulated cable. A stranded cable can have a different physical diameter even when its nominal metal area is comparable.

Ampacity is a separate reference

Ampacity is the current a conductor can carry under specified conditions. It depends on the conductor material, insulation, installation environment, temperature, grouping and termination restrictions, among other factors. Geometry alone cannot answer it. The selected copper ampacity reference reproduces only three verified manufacturer data rows with their scope and limitations. It is not a complete current-rating table. Consult the applicable edition of electrical standards, product documentation and a qualified professional. The voltage drop calculator estimates loss from supplied conductor resistance data and is not a substitute for an ampacity analysis.

Use a reference value correctly

Check whether a value describes real power, apparent power, stored energy or charge before entering it. When comparing values, first bring the units into a consistent scale. For a manufacturer rating, retain its test conditions and distinguish nominal and measured values. Rounding in these tables is intended for quick comparison; a more precise calculation may produce slightly different displayed values. Use unit conversions for the corresponding interactive tools and the formula library for definitions and worked examples.