Voltage Drop Calculator (AC & DC)

Estimate DC, single-phase or balanced three-phase voltage drop from current or real power, length and known conductor impedance. See volts and percentage loss.

CALCULATOR WORKSPACE Live calculation
Estimated voltage drop—

Voltage budget

LIVE VIEW
Supply—
Cable loss—
Load voltage—

Bars share a common scale within this view.

Calculate voltage drop for DC and AC

Select DC, single-phase AC or balanced three-phase AC. Enter supply voltage, one-way length, conductor resistance and either load current or real electrical input power. AC requires known reactance and lagging power factor. The model is an approximate steady-state voltage-loss calculation, not a cable sizing or compliance decision.

Equations and units

Let L be one-way length in kilometers, I current in amperes, R resistance and X inductive reactance in ohms per kilometer, and PF the lagging displacement power factor under sinusoidal conditions.

Circuit Approximate voltage drop
DC, two conductors 2 × I × L × R
Single-phase AC, two conductors 2 × I × L × (R × PF + X × √(1 − PF²))
Balanced three-phase AC √3 × I × L × (R × PF + X × √(1 − PF²))

The tool divides entered meters by 1,000. Percentage drop equals 100 × voltage drop / supply voltage. For three-phase AC, the voltage is line-to-line RMS voltage and power is total real input power across the phases. With power input, the current estimate uses the entered supply voltage, not a solved receiving-end voltage.

Worked DC example

For a mathematical model with 24 V, 5 A, 10 m one-way length and 5 Ω/km resistance per conductor, the round-trip resistance is 0.1 Ω. The drop is 0.5 V, or about 2.083% of supply voltage. The estimated remaining voltage is 23.5 V.

Single-phase AC example

For hypothetical inputs of 120 V, 10 A, 20 m, R = 4 Ω/km, X = 0.2 Ω/km and PF = 0.8, the sine term is 0.6. The effective longitudinal term is 3.32 Ω/km and the approximate drop is 1.328 V (1.107%). This example is arithmetic only; the impedance values are illustrative, not cable specifications.

Balanced three-phase example

For hypothetical inputs of 400 V line-to-line, 15 A, 30 m, R = 2 Ω/km, X = 0.1 Ω/km and PF = 0.9, the longitudinal term is about 1.84359 Ω/km. Multiplying by √3, 15 A and 0.03 km gives about 1.437 V, or 0.359% of the entered voltage.

Interpreting the approximation

DC uses a resistive return path. In AC, resistance and reactance contribute differently depending on phase angle. The voltage-drop expression approximates the longitudinal change in voltage magnitude; it is not an exact phasor solution for all conditions. Leading power factor, unbalanced circuits, harmonics, temperature variation, fault conditions and motor starting are outside the model.

Use known cable impedance from the manufacturer or appropriate engineering data at the relevant operating conditions. An AWG designation alone does not determine AC impedance, allowable current or actual resistance at temperature. If the estimate approaches or exceeds supply voltage, the model cannot describe a physically suitable operating point. Zero current or length produces zero estimated loss. When calculating current from real power, power factor must be positive.

Related references

See watts to amps, kW to amps, AWG geometry and calculation methodology. The Seattle Public Utilities electrical design calculations guide and Schneider Electric Electrical Installation Guide describe the voltage-drop relationships.

This calculator is for educational estimates. It does not establish acceptable voltage drop, conductor ampacity, protective-device selection or code compliance. Actual installations require applicable standards, equipment data and qualified electrical review.

Compare circuit models with stated impedance

The table uses the same hypothetical 10 A load current, R = 2 Ω/km and X = 0.1 Ω/km with lagging displacement PF 0.8 for AC. The DC model uses R only. Each column is the approximate loss in volts; these are arithmetic model comparisons, not conductor ratings.

One-way length DC pair Single-phase AC Balanced 3-phase AC
1 m 0.04 0.0332 0.028752
2 m 0.08 0.0664 0.057504
5 m 0.2 0.166 0.14376
10 m 0.4 0.332 0.28752
15 m 0.6 0.498 0.43128
20 m 0.8 0.664 0.57504
30 m 1.2 0.996 0.86256
50 m 2 1.66 1.4376
75 m 3 2.49 2.1564
100 m 4 3.32 2.8752
150 m 6 4.98 4.3128
200 m 8 6.64 5.7504

The models are not interchangeable, and the current and impedance in this example are supplied hypothetical quantities. The table does not predict the actual current of an equipment load under different supply conditions.

Input current or input real power

If current is already known, choose the current input. If real electrical input power is known, the tool first estimates the current using the selected supply type, entered supply voltage and, for AC, positive power factor. The power input is in watts and not kVA or mechanical output.

For example, an illustrative single-phase operating point with 960 W real power, 120 V RMS and PF 0.8 corresponds to 10 A in the simplified input-current model. The tool then uses that estimated current in its approximate impedance calculation. This is not an iterative load-flow solution or a receiving-end voltage model.

Resistance per kilometer and total resistance

The resistance and reactance inputs are per conductor per kilometer at the relevant conditions. Do not enter a total round-trip resistance into the per-kilometer field. The tool converts one-way meters to kilometers and includes the appropriate path or balanced-phase multiplier. A data sheet reporting ohms per 1,000 feet uses a different distance unit; the corresponding value in Ω/km is the original value divided by 0.3048.

Actual AC resistance and reactance depend on cable construction, operating temperature, frequency and arrangement. A nominal gauge or a bare conductor diameter alone does not supply all of these quantities. Use verified product or engineering data rather than treating the illustrative values in the table as specifications.

Interpreting the percentage

The percentage calculation uses the entered supply voltage as its denominator. The same loss in volts represents a different percentage at a different voltage. For example, a hypothetical 0.5 V loss corresponds to about 2.083% of 24 V and 0.417% of 120 V. This comparison does not establish an acceptable voltage-drop limit for either operating condition.

Large calculated losses can invalidate the approximation; the tool warns if the result equals or exceeds the entered supply voltage. For actual installation limits, conductor ratings and applicable rules, qualified electrical assessment is needed. The wire-size ideal-area calculator covers a different mathematical geometry problem and does not determine compliance.

Frequently asked questions

Why does the DC formula double the cable length?

The model assumes equal outgoing and return conductors, each of the entered one-way length.

What is needed for the AC model?

Use RMS quantities, resistance and inductive reactance at the relevant operating conditions, and lagging power factor. Three-phase mode assumes a balanced load.

Does this calculate safe wire size?

No. This is a steady-state approximate model, not an ampacity, protection, equipment selection or installation compliance calculation.