Watts to Amps Calculator
Convert watts to amps using voltage and AC power factor. Calculate DC, single-phase or balanced three-phase current and see 12 V, 120 V and 240 V examples.
Current vs. voltage
LIVE VIEWAt constant power and power factor, higher voltage corresponds to lower current.
How to convert watts to amps
Choose the supply type, enter real power in watts and voltage in volts. For AC, enter the power factor. Three-phase mode assumes a balanced load and line-to-line RMS voltage.
| Supply | Formula |
|---|---|
| DC | I = P / V |
| Single-phase AC | I = P / (V × PF) |
| Balanced three-phase AC | I = P / (√3 × VLL × PF) |
Worked examples
A 1,000 W DC load at 120 V draws 8.333 A. A single-phase 1,000 W load at 120 V with power factor 0.8 draws 10.417 A. A balanced 9,000 W three-phase load at 400 V and power factor 0.9 draws approximately 14.434 A.
Reference chart at unity power factor
| Power | 12 V DC | 120 V DC | 240 V DC |
|---|---|---|---|
| 100 W | 8.33 A | 0.83 A | 0.42 A |
| 500 W | 41.67 A | 4.17 A | 2.08 A |
| 1000 W | 83.33 A | 8.33 A | 4.17 A |
| 1500 W | 125 A | 12.50 A | 6.25 A |
These are mathematical examples, not recommended circuit ratings. Motor input power differs from shaft output power; efficiency and starting current may matter. Do not use the result alone to select wiring, breakers or protective devices.
Related resources
Ohm’s law calculator · Electrical formulas · Units reference
See our calculation methodology.
What changes the answer?
At fixed input power and power factor, doubling voltage halves the current. At a fixed voltage of 120 V, 600 W corresponds to 5 A for DC or unity-PF single-phase AC; at PF 0.75 the single-phase result is 6.67 A. The interactive curve illustrates the first relationship. It holds power and power factor constant rather than modeling an actual device's response to voltage changes.
Watts, VA and motor ratings
Watts measure real power; VA measure apparent power. If a rating is stated in kVA, use the kVA to amps calculator, not the real-power formula. If a rating is mechanical shaft output, efficiency is also needed to estimate real electrical input. Power factor and efficiency describe different relationships. A zero power factor makes the inverse real-power-to-current calculation indeterminate, so the tool requires positive PF for AC.
References: OpenStax, AC circuit power and Fluke, balanced three-phase AC power.
How many amps are 1,000, 1,500 and 2,000 watts?
The following table uses DC or a single-phase AC load with unity power factor. The figures are mathematical operating points and are not recommended circuit ratings.
| Real power | 12 V | 120 V | 240 V |
|---|---|---|---|
| 1,000 W | 83.33 A | 8.33 A | 4.17 A |
| 1,500 W | 125.00 A | 12.50 A | 6.25 A |
| 2,000 W | 166.67 A | 16.67 A | 8.33 A |
1,000 watts to amps: at 12 V, 1,000 ÷ 12 = 83.33 A; at 120 V, 1,000 ÷ 120 = 8.33 A; at 240 V, 1,000 ÷ 240 = 4.17 A.
1,500 watts to amps: at 12 V, 1,500 ÷ 12 = 125 A; at 120 V, 1,500 ÷ 120 = 12.5 A; at 240 V, 1,500 ÷ 240 = 6.25 A.
2,000 watts to amps: at 12 V, 2,000 ÷ 12 = 166.67 A; at 120 V, 2,000 ÷ 120 = 16.67 A; at 240 V, 2,000 ÷ 240 = 8.33 A.
For a single-phase AC example with PF = 0.8, 1,500 W at 120 V corresponds to 15.625 A instead of 12.5 A. At 240 V and the same PF it corresponds to 7.8125 A. The examples are not an instruction to change the supply voltage of any equipment.
Which supply type should I select?
Select DC when the inputs describe a direct-current operating point. For single-phase AC, voltage and current are RMS quantities and power is real electrical power. For balanced three-phase AC, use the total real power across the phases and line-to-line RMS voltage, not power per phase. If a three-phase load is unbalanced, the balanced formula is insufficient.
A 6,000 W balanced three-phase load with 400 V line-to-line voltage and PF 0.8 has a calculated line current of 6,000 ÷ (√3 × 400 × 0.8), approximately 10.83 A. Using the single-phase equation on those same inputs would give 18.75 A and would answer a different question.
What if the label shows different units?
Convert kilowatts to watts by multiplying by 1,000, or use the kW to amps calculator. If the label uses apparent power in kVA rather than real power, use the kVA to amps calculator. A battery energy rating in Wh is not a watt rating; energy alone does not establish the instantaneous current.
Motor shaft output is not automatically electrical input power. The input rating or measured electrical power is preferable. If only shaft output is known, an appropriate efficiency assumption is also needed; efficiency is not power factor.
Check your inputs and interpret the result
A zero voltage or zero AC power factor cannot provide a finite unique inverse result using this model. A zero real power with positive voltage and power factor produces zero current in the simplified equation. The graph holds power and PF fixed, so it does not predict how an actual device behaves when its voltage changes. A displayed current is not a wiring, breaker, equipment or safety approval.
As a numerical cross-check, multiply the calculated DC current by voltage to recover the entered watts, or use amps to watts with the same supply assumptions. The OpenStax electrical power discussion explains the underlying relationship; its AC power chapter distinguishes RMS values and phase effects.
Frequently asked questions
Can watts be converted to amps without voltage?
No. You need voltage and, for AC real power, the relevant power factor and phase configuration.
How many amps is 1500 watts at 120 volts?
12.5 A for DC or a single-phase load with unity power factor. Other AC loads may draw more current.