kW to Amps Calculator
Convert real power in kilowatts to amps using voltage and AC power factor. Calculate DC, single-phase and balanced three-phase current with examples.
Formula and units
DC: I = 1000 × P / V. Single-phase AC: I = 1000 × P / (V × PF). Balanced three-phase AC: I = 1000 × P / (√3 × VLL × PF). P is in kW.
Use RMS voltage and current for AC. Three-phase equations assume a balanced load and line-to-line voltage. Convert kW to W before calculating current. Motor shaft power is not electrical input power; account for efficiency separately.
Worked examples
A 2 kW DC load at 100 V draws 20 A. A 2 kW single-phase load at 230 V and PF 0.8 draws approximately 10.87 A. A balanced 15 kW load at 400 V and PF 0.9 draws approximately 24.06 A.
How to interpret the result
The output is current in amperes, not energy consumption or an equipment rating. Input values are treated as steady-state quantities. For changing loads, use an appropriate measurement or estimate rather than assuming a single operating value covers all conditions. Display rounding does not increase measurement accuracy.
Related calculations
Watts to amps · Ohm’s law · Electrical formulas · Conversions
This is an educational calculation, not an installation approval. See our methodology.
Read the rating before converting
A kilowatt value is 1,000 watts. If a label states 4 kW of real electrical input and the hypothetical supply is 230 V single-phase with PF 0.8, the estimated current is about 21.74 A. In balanced three-phase mode, 4 kW at 400 V and the same PF corresponds to approximately 7.22 A. These examples compare mathematical operating points, not alternative wiring choices.
If the label gives mechanical output, the electrical input is not the same quantity. If the label gives kVA, use kVA to amps. For watt-based inputs, use watts to amps. Never use the calculated current alone to select protection or determine safe installation conditions.
Reference: Fluke, balanced three-phase AC power.
kW to amps reference at common voltages
The table uses two stated AC examples alongside the DC relationship. Results are amperes and assume total real electrical input, not motor shaft output. Three-phase voltage is line-to-line RMS voltage.
| Real power | 120 V DC | 240 V DC | 230 V 1-phase, PF 0.8 | 400 V 3-phase, PF 0.8 |
|---|---|---|---|---|
| 0.5 kW | 4.1667 | 2.0833 | 2.7174 | 0.90211 |
| 1 kW | 8.3333 | 4.1667 | 5.4348 | 1.8042 |
| 1.5 kW | 12.5 | 6.25 | 8.1522 | 2.7063 |
| 2 kW | 16.667 | 8.3333 | 10.87 | 3.6084 |
| 3 kW | 25 | 12.5 | 16.304 | 5.4127 |
| 4 kW | 33.333 | 16.667 | 21.739 | 7.2169 |
| 5 kW | 41.667 | 20.833 | 27.174 | 9.0211 |
| 7.5 kW | 62.5 | 31.25 | 40.761 | 13.532 |
| 10 kW | 83.333 | 41.667 | 54.348 | 18.042 |
| 15 kW | 125 | 62.5 | 81.522 | 27.063 |
| 20 kW | 166.67 | 83.333 | 108.7 | 36.084 |
| 30 kW | 250 | 125 | 163.04 | 54.127 |
At the same real power and voltage, reducing the power factor raises the mathematical current in an AC operating-point calculation. A three-phase result uses the appropriate balanced-circuit multiplier. These numbers do not establish permissible current ratings for actual wiring or equipment.
Check the scale before entering kilowatts
An input of 1.5 kW means 1,500 W. If a label states 750 W, enter 0.75 kW. A hypothetical 0.75 kW DC load at 120 V corresponds to 6.25 A. Entering 750 in the kilowatt field would represent a completely different power magnitude.
Kilowatt-hours are not kilowatts. If the known quantity is accumulated energy, divide energy in kWh by elapsed hours to estimate average kW across that interval. That average does not identify peak or instantaneous current. See power vs energy for the distinction.
Real power, apparent power and horsepower
This page starts from real electrical input power. A kVA rating describes apparent power and belongs in the kVA to amps calculator. A mechanical horsepower rating needs an additional efficiency assumption before it can be related to electrical input. See HP to amps for the stated mathematical model.
For a hypothetical real-power operating point of 4 kW at PF 0.8, apparent power is 5 kVA. With 400 V line-to-line balanced three-phase voltage, either the real-power formula or the apparent-power formula gives approximately 7.217 A. The consistency check works because all values describe the same assumptions.
How to choose an AC voltage input
For single-phase AC, use the RMS voltage of the circuit under consideration. For balanced three-phase AC, use the line-to-line RMS voltage and total real power. Do not enter the per-phase power in a field intended for total power. The calculator does not determine whether an actual electrical installation uses either configuration.
What the result means
The calculated current is a steady-state operating-point estimate. Changes in load, motor starting, thermal effects, unbalanced phases and equipment specifications can alter actual conditions. A zero power factor or voltage cannot provide a finite unique inverse result, so the tool requires positive values for those denominators. With a positive denominator, zero real power returns zero in the simplified model.
Use amps to kW for a reverse check and watts to amps if the original input is in watts. Do not use the result alone to determine wiring or protection.
Frequently asked questions
What information does this calculation require?
Convert kW to W before calculating current. Motor shaft power is not electrical input power; account for efficiency separately.
Can I use the result to choose a breaker?
No. Protective equipment selection requires additional installation and equipment information and applicable standards.