HP to Amps Calculator
Estimate electrical input current from mechanical horsepower, voltage, efficiency and AC power factor. Supports DC, single-phase and balanced three-phase.
Estimate current from mechanical horsepower
Horsepower measures a rate of power, and amperes measure electrical current. A motor's mechanical shaft power is not equal to its electrical input power unless efficiency is ideal. To estimate electrical current from a specified shaft output, convert mechanical horsepower to watts, divide by the efficiency fraction, and then apply the relevant DC or AC power relationship. This is a steady-state arithmetic estimate, not a motor sizing or nameplate current tool.
Equations and required quantities
One mechanical horsepower equals approximately 745.6999 W. Let H be mechanical horsepower, η the efficiency fraction, V the operating voltage, and PF the AC power factor. Estimated input real power is P = H × 745.6999 / η. DC current equals P / V, single-phase AC current equals P / (V × PF), and balanced three-phase AC current equals P / (√3 × VLL × PF).
The efficiency entry is a percentage: 85 means 0.85 in the equation. Power factor is a ratio: enter 0.8 rather than 80. AC uses RMS voltage and current; balanced three-phase uses line-to-line voltage and total shaft output. Do not substitute electrical horsepower or metric horsepower without checking the definition.
Worked examples and comparison chart
Consider hypothetical shaft output of 1 hp and efficiency of 85%. The estimated input real power is 877.29 W. At 120 V single-phase and PF 0.8, the model gives approximately 9.14 A. At 400 V balanced three-phase with the same illustrative efficiency and PF, it gives about 1.58 A.
| Mechanical output | Electrical input at 85% | 120 V single-phase, PF 0.8 | 400 V three-phase, PF 0.8 |
|---|---|---|---|
| 0.25 hp | 0.219 kW | 2.28 A | 0.40 A |
| 0.5 hp | 0.439 kW | 4.57 A | 0.79 A |
| 1 hp | 0.877 kW | 9.14 A | 1.58 A |
| 1.5 hp | 1.316 kW | 13.71 A | 2.37 A |
| 2 hp | 1.755 kW | 18.28 A | 3.17 A |
| 3 hp | 2.632 kW | 27.42 A | 4.75 A |
| 5 hp | 4.386 kW | 45.69 A | 7.91 A |
| 7.5 hp | 6.580 kW | 68.54 A | 11.87 A |
| 10 hp | 8.773 kW | 91.38 A | 15.83 A |
The inputs are deliberately illustrative. Actual efficiency and power factor are not fixed at these values, and can vary with loading, equipment and operating conditions. The chart does not report standardized full-load amperes, starting current or required protection.
Efficiency and power factor are different
Efficiency compares mechanical output with real electrical input. Power factor compares real electrical input with apparent electrical power. For example, a hypothetical motor delivering 750 W mechanically with 75% efficiency consumes 1,000 W real electrical power in this simple model. If its PF is 0.8, the corresponding apparent power is 1.25 kVA. These two ratios must not be substituted for each other.
When not to use this estimate
A nameplate current or manufacturer performance data are preferable for actual equipment. Motor starting behavior, duty cycle, temperature, harmonics, supply variations and installation requirements are not represented. The calculator requires positive voltage, efficiency and AC power factor, and cannot determine a safe motor circuit rating. A zero mechanical output with fixed positive efficiency is only an ideal mathematical boundary, not a real motor no-load model.
Related tools
When the real electrical input is already known, use watts to amps or kW to amps. When the rating is apparent power, use kVA to amps. The mechanical horsepower coefficient comes from NIST conversion factors. See also calculation methodology.
Convert mechanical output units consistently
If a shaft rating is already given in watts, the horsepower conversion is unnecessary. Divide the known mechanical output by the efficiency fraction to estimate real electrical input under the stated model, then use the appropriate power-to-current converter. If efficiency or power factor has not been supplied by a reliable source for the relevant operating point, the current cannot be determined from horsepower alone. Do not substitute an assumed percentage into an equipment selection decision.
How to check the estimated real input
The tool displays its intermediate real power estimate in watts. This quantity is separate from the final current estimate. Multiply the calculated current by the entered voltage and, in AC, the relevant power factor and phase multiplier to recover the intermediate input power. This check helps identify inconsistent units, but cannot establish that the assumed efficiency and power factor describe actual equipment. A calculation from assumed mechanical output is not a substitute for a measured input current or verified manufacturer rating.