Watts to Volts Calculator

Convert real power in watts to voltage using current and AC power factor. See equations for DC, single-phase and balanced three-phase operating points.

CALCULATOR WORKSPACE Live calculation
Calculated voltage—

Convert watts to volts

For DC, divide real power in watts by current in amperes. For AC, select the appropriate circuit type and supply RMS current and power factor. The balanced three-phase result is line-to-line RMS voltage.

Circuit Equation
DC V = P / I
Single-phase AC V = P / (I × PF)
Balanced three-phase AC VLL = P / (√3 × I × PF)

Examples

A 1200 W DC load drawing 10 A corresponds to 120 V. A 960 W single-phase load drawing 10 A at PF 0.8 corresponds to 120 V RMS. A balanced three-phase load of 9000 W drawing 15 A at PF 0.9 corresponds to about 384.9 V line-to-line.

Interpretation

These equations describe relationships at a specified operating point. They do not establish a safe supply voltage, insulation rating or suitable power source. Actual loads may be nonlinear, unbalanced or time varying. Use measured or rated electrical input power rather than motor shaft output.

Related tools

Volts to watts · Watts to amps · Ohm’s law.

A calculated voltage is not a supply specification

For a hypothetical DC operating point of 48 W and 4 A, the equation returns 12 V. For single-phase AC with 48 W, 4 A RMS and PF 0.8, the corresponding voltage is 15 V RMS. The difference results from the assumed power factor. These examples are relationships between specified quantities, not a method for choosing a safe voltage for equipment.

Current and AC power factor must be positive for this inverse calculation. A zero denominator cannot identify a unique voltage from the given real power. In balanced three-phase mode the result refers to line-to-line RMS voltage, not phase-to-neutral voltage. Use volts to watts to check the inverse calculation.

Reference: Fluke, balanced three-phase AC power.

Voltage reference table for fixed power and current

The following entries use the DC relationship V = P / I. They are mathematical operating points, not voltage recommendations or instructions to select a power supply.

Real power 0.5 A 1 A 2 A 5 A 10 A
5 W 10 V 5 V 2.5 V 1 V 0.5 V
10 W 20 V 10 V 5 V 2 V 1 V
20 W 40 V 20 V 10 V 4 V 2 V
25 W 50 V 25 V 12.5 V 5 V 2.5 V
50 W 100 V 50 V 25 V 10 V 5 V
100 W 200 V 100 V 50 V 20 V 10 V
120 W 240 V 120 V 60 V 24 V 12 V
240 W 480 V 240 V 120 V 48 V 24 V
500 W 1000 V 500 V 250 V 100 V 50 V
1000 W 2000 V 1000 V 500 V 200 V 100 V

For instance, an illustrative 24 W operating point with 2 A corresponds to 12 V. At the same specified power with 1 A, the equation returns 24 V. These comparisons do not imply an actual load can operate at both voltages.

What happens when AC power factor changes?

In the single-phase model, if 120 W of real power and 2 A RMS are specified, unity PF corresponds to 60 V RMS. At PF 0.8, the corresponding mathematical voltage is 75 V RMS. In balanced three-phase mode, the formula also contains the square-root-of-three multiplier because total real power is spread across the balanced phases.

The calculator treats current, power and power factor as supplied operating-point information. It does not solve a real load's impedance, find a safe voltage or predict how a device responds to changing its supply. For AC, the positive PF input must describe the specified operating condition.

Identify power and current scales

If a power value is expressed in kilowatts, multiply it by 1,000 before entering watts. If current is expressed in milliamperes, divide by 1,000 before entering amperes. For a hypothetical 0.2 W and 25 mA DC operating point, use 0.2 W and 0.025 A; the result is 8 V.

Do not substitute kVA for watts. Apparent power and real power are related through power factor. The kVA to kW calculator can convert those quantities when PF is known. An energy rating in Wh is not an instantaneous power rating.

Use resistance when it is the quantity you know

If you know an ideal DC resistance and current, the relevant voltage relationship is V = I × R rather than division of power by current. The Ohm’s law calculator supports that model. If you know voltage and power, use volts to amps to calculate the corresponding current.

Check inverse calculations and boundaries

With positive current and the appropriate positive AC PF, multiply the computed voltage by current and any phase/PF factors to recover the original watts. Use volts to watts for that inverse check. A zero current with nonzero power cannot identify a finite voltage in this model; zero power and zero current are also insufficient to determine a unique voltage. The tool rejects a zero denominator.

A numerical result cannot establish supply compatibility. Equipment ratings, transients, installation conditions and electrical safety are separate considerations. See why voltage and PF matter and calculation methodology.

Frequently asked questions

Can watts alone determine voltage?

No. You also need current and, for AC real power, power factor and phase configuration.