Volts to Amps Calculator
Find current from voltage and real power for DC, single-phase or balanced three-phase AC, or from voltage and resistance in an ideal DC model.
Voltage alone cannot identify current
Voltage measures potential difference, while current measures the rate of charge flow. Current depends on the other quantities describing a circuit. This tool supports two different mathematical tasks: current from real electrical power and voltage, and current from voltage and a known ideal linear resistance in DC. Choose the model based on the information you have.
Current from real power
For DC, I = P / V. For single-phase AC, I = P / (V × PF). For balanced three-phase AC, I = P / (√3 × VLL × PF). P is real electrical input power in watts; AC voltage and current are RMS quantities. For example, an ideal 120 W DC operating point at 12 V corresponds to 10 A. A hypothetical single-phase 960 W load at 120 V and PF 0.8 also corresponds to 10 A.
Current from known resistance
For an ideal linear DC resistor, I = V / R. A 3 V potential difference across a hypothetical 150 Ω resistance corresponds to 0.02 A, or 20 mA. This is a mathematical example, not advice on energizing any real device. A resistance value is not a substitute for a known AC impedance in a general AC circuit.
DC and unity-PF current comparison
| Voltage | 100 W | 500 W | 1,000 W |
|---|---|---|---|
| 5 V | 20.000 A | 100.000 A | 200.000 A |
| 12 V | 8.333 A | 41.667 A | 83.333 A |
| 24 V | 4.167 A | 20.833 A | 41.667 A |
| 48 V | 2.083 A | 10.417 A | 20.833 A |
| 120 V | 0.833 A | 4.167 A | 8.333 A |
| 230 V | 0.435 A | 2.174 A | 4.348 A |
| 240 V | 0.417 A | 2.083 A | 4.167 A |
| 400 V | 0.250 A | 1.250 A | 2.500 A |
| 480 V | 0.208 A | 1.042 A | 2.083 A |
These are fixed-power examples under the mathematical DC model or unity-PF single-phase AC. They are not typical current ratings, and the result changes when the load's power or its operating conditions change. The chart does not imply that an actual device will draw constant power across different voltages.
Which model should I choose?
If you have voltage and a measured real power input, use the power mode. If you have a known DC resistance value and the potential difference across it, choose resistance mode. For AC real-power conversion, identify the supply type and power factor. In balanced three-phase mode, use total real power and line-to-line RMS voltage.
If the input label states apparent power in kVA, use kVA to amps instead. If the power is given in kilowatts, use kW to amps. If you only need to solve the ideal resistance relationship, the Ohm’s law calculator also supports voltage and resistance calculations.
Common unit mistakes
Enter watts, not kilowatts, in the power field; multiply kW by 1,000 first. Enter ohms, not kilohms, in the resistance field; multiply kΩ by 1,000 first. The result is displayed in amperes. A result of 0.025 A is 25 mA. Avoid using peak sinusoidal voltage in place of RMS voltage in AC mode.
What the result does not establish
The power-mode equation uses a specified operating point and does not model startup, nonlinear loads, changes of resistance with temperature or other transient effects. The resistance mode is limited to an ideal linear DC model. A zero denominator cannot identify a finite current; negative inputs are outside these nonnegative magnitude models. These calculations do not establish safe supply conditions, allowable conductor current or equipment ratings.
For further reading, consult electrical formulas, DC vs AC and OpenStax, Ohm’s law.
Check current against the original inputs
A 10 A result from the DC power mode with an entered voltage of 12 V corresponds to 120 W under that same model. In resistance mode, a result of 0.02 A with 150 Ω gives 3 V when multiplied. This is a useful dimensional and arithmetic check, but not an independent validation of actual equipment conditions.
What happens when voltage is zero?
In the ideal resistance mode, zero voltage across a positive resistance gives zero current. In the power mode, zero voltage is not a valid denominator. The same number therefore has different meanings depending on the equation. Use the appropriate mode rather than trying to resolve this distinction by entering an artificial small voltage.