AWG Wire Gauge Chart

Look up nominal AWG wire diameter in inches and millimeters and cross-sectional area in mm². Compare 4/0 through 37 AWG; this is not an ampacity chart.

CALCULATOR WORKSPACE Live calculation
—

AWG diameter and cross-sectional area

AWGDiameter (in)Diameter (mm)Area (mm²)
00000.4600011.6840107.2193
0000.4096410.404985.0288
000.364809.265867.4309
00.324868.251553.4751
10.289307.348142.4077
20.257636.543733.6308
30.229425.827326.6705
40.204315.189421.1506
50.181944.621316.7732
60.162024.115413.3018
70.144293.664910.5488
80.128493.26368.3656
90.114422.90646.6342
100.101902.58825.2612
110.090742.30484.1723
120.080812.05253.3088
130.071961.82782.6240
140.064081.62772.0809
150.057071.44951.6502
160.050821.29081.3087
170.045261.14951.0378
180.040301.02370.8230
190.035890.91160.6527
200.031960.81180.5176
210.028460.72290.4105
220.025350.64380.3255
230.022570.57330.2582
240.020100.51060.2047
250.017900.45470.1624
260.015940.40490.1288
270.014200.36060.1021
280.012640.32110.0810
290.011260.28590.0642
300.010030.25460.0509
310.008930.22680.0404
320.007950.20190.0320
330.007080.17980.0254
340.006300.16010.0201
350.005610.14260.0160
360.005000.12700.0127
370.004450.11310.0100

How to read the AWG chart

The American Wire Gauge system describes nominal sizes of round conductors. The chart covers 0000 (4/0) through 37 AWG. Select a gauge above to see its nominal diameter and circular cross-sectional area. Values describe bare solid round conductors, not the outside diameter of insulated cable.

AWG diameter formula

For gauge n, diameter in millimeters is d = 0.127 × 92^((36 − n)/39). Use n = 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0. Cross-sectional area is πd²/4. Diameter in inches is d/25.4.

Worked example

12 AWG has a nominal diameter of approximately 2.0525 mm and cross-sectional area of 3.31 mm². A 6 AWG conductor is approximately twice the diameter of 12 AWG, or approximately four times the area.

Diameter is not ampacity

Stranded conductors have different physical outside diameters because of gaps between strands and construction. Insulation increases the outside diameter further. The chart is not a current rating table. Do not use diameter alone to select a conductor for an installation.

Related resources

Electrical units · Ohm’s law · Watts to amps. For the units used here, consult the NIST SI guide.

Comparing neighboring gauges

AWG is logarithmic: the nominal diameter ratio between adjacent sizes is about 1.123. A change of three gauge numbers corresponds to approximately a factor of two in cross-sectional area. For example, 12 AWG is about 3.31 mm² and 15 AWG is about 1.65 mm². A smaller gauge number therefore denotes a larger nominal conductor. These comparisons concern geometry, not allowable current.

Reference verification

The historical NBS Copper Wire Tables, Handbook 100, Table 5 gives 4/0 AWG as 460 mils (11.684 mm) and 36 AWG as 5 mils (0.127 mm). The chart uses the geometric AWG relationship between these endpoints; rounded printed reference values may differ slightly from formula-generated values. One mil is 0.001 inch.

For a real cable, use the manufacturer's resistance data at the relevant operating temperature. The DC voltage drop calculator accepts a known resistance per conductor rather than assuming a wire material or allowable ampacity.

Common AWG sizes in millimeters and square millimeters

The two metric columns answer different questions. Diameter is a length; cross-sectional area is a surface area. Use the diameter column when comparing nominal round-wire thickness, and the area column when comparing the amount of conductor cross section.

Gauge Diameter (mm) Area (mm²)
1/0 8.2515 53.4751
2 6.5437 33.6308
4 5.1894 21.1506
6 4.1154 13.3018
8 3.2636 8.3656
10 2.5882 5.2612
12 2.0525 3.3088
14 1.6277 2.0809
16 1.2908 1.3087
18 1.0237 0.8230
20 0.8118 0.5176
22 0.6438 0.3255
24 0.5106 0.2047
26 0.4049 0.1288
28 0.3211 0.0810
30 0.2546 0.0509
32 0.2019 0.0320
34 0.1601 0.0201
36 0.1270 0.0127

The figures are calculated nominal solid-conductor values, rounded for display. AWG 14 is about 1.63 mm in diameter and 2.08 mm² in area; AWG 12 is about 2.05 mm in diameter and 3.31 mm² in area. The change from 14 to 12 is two gauge steps, not a linear increase of two millimeters.

How do 1/0, 2/0, 3/0 and 4/0 fit into AWG?

The zero-based sizes extend the same logarithmic sequence. A designation of 1/0 corresponds to n = 0 in the equation, 2/0 to n = −1, 3/0 to n = −2 and 4/0 to n = −3. As the number of zeros increases, nominal conductor diameter and area increase. The calculator uses the same expression for these larger sizes rather than a separate conversion factor.

A 4/0 conductor has approximately 11.684 mm nominal diameter and 107.22 mm² nominal area. The figure is a bare solid-round equivalent, not the outside diameter of a stranded or insulated product.

Convert a nominal diameter back to an AWG estimate

The logarithmic relationship can be reversed for a positive diameter d in millimeters: n = 36 − 39 × ln(d / 0.127) / ln(92). If the diameter is 2.00 mm, the calculated index is roughly 12.2, close to nominal 12 AWG. This is a geometry comparison only. A measured diameter may differ because of construction, plating, insulation, tolerances or the measuring instrument.

A known circular area can also be converted to a diameter using d = √(4A / π). For a hypothetical 2.5 mm² round section, the equivalent diameter is about 1.784 mm. That does not mean a metric-designated cable is interchangeable with an AWG product.

Area, resistance and construction

For an ideal homogeneous conductor of fixed material, length and temperature, electrical resistance is inversely proportional to cross-sectional area. Doubling the area halves the resistance in that model. The relationship does not establish allowable current, and actual cable resistance depends on the construction and operating conditions. Use the manufacturer's resistance specification when using our DC voltage drop calculator.

A stranded conductor's total metal area is the relevant geometry; the bundle may have air gaps and therefore a different measured outside diameter. Insulation adds more thickness and is not included in the AWG chart. Do not infer wire gauge from insulation thickness or use the chart to choose a protective device.

Is an AWG chart an ampacity chart?

No. An ampacity table answers a separate question involving installation conditions, conductor material, insulation, temperature, applicable rules and more. This page deliberately provides geometry rather than assigning current ratings. Consult the relevant product data and qualified professionals for actual installations. For historical background, the NBS Copper Wire Tables documents standard wire geometry and other properties.

Frequently asked questions

Does a lower AWG number mean a thicker wire?

Yes. In the AWG system, smaller gauge numbers represent larger nominal conductor diameters.

Does AWG specify safe current?

No. Ampacity depends on conductor material, insulation, installation conditions and applicable electrical standards.