Ampacity Chart (Selected Copper Product Data)

Compare selected manufacturer-published copper conductor ampacity reference values at 75°C and 90°C, with product scope and important code limitations.

CALCULATOR WORKSPACE Live calculation

Product-specific reference only: Southwire SPEC 10003, Table 2, updated October 30, 2026; based on 2023 NEC Table 310.16. Not a safe current or breaker selector.

Published product reference—
AWG75°C column90°C column
1420 A25 A
1225 A30 A
1035 A40 A

Source notes explicitly exclude certain small-conductor overcurrent-protection limits and require additional NEC provisions. Do not use these values as breaker ratings or as an installation approval.

View original product data and notes

What an ampacity chart represents

Ampacity refers to current carrying capacity under defined conditions. The values above are a deliberately limited product-specific reference, not a reproduction of the complete National Electrical Code ampacity tables. They come from Southwire's SPEC 10003 for copper THHN/THWN-2 silicone-free conductors, Table 2, revision 1.000.046 updated October 30, 2026. The manufacturer identifies its values as based on 2023 NEC Table 310.16. See the linked original product page for the complete notes.

How to read the two temperature columns

The headings refer to the temperature columns used in the manufacturer's published ampacity data. They are not a choice that a user can make simply by selecting the higher number. The actual applicable column and limits depend on the complete installation, conductor rating, terminations, equipment, ambient conditions, grouping and adopted requirements. The product specification lists multiple application ratings, illustrating why a single temperature label does not answer every installation question.

The chart gives the same published reference columns for 14, 12 and 10 AWG in the selected product family. It does not extrapolate to other gauges, aluminum conductors or unrelated cable types. If the product or conductor configuration differs, consult its own technical data.

Why an ampacity reference is not a breaker chart

The source specifically warns that its ampacity values do not incorporate certain overcurrent protection restrictions for small copper conductors under NEC 240.4(D). It also refers readers to additional requirements in NEC 310.15 and 110.14(C). These references matter because published conductor ampacity alone does not determine an acceptable protective device or circuit. The values displayed on this page must not be used to infer a breaker size.

Gauge and ampacity are not the same measurement

AWG describes nominal conductor geometry. For a round conductor, nominal area increases as gauge number decreases. But geometry alone does not define current carrying capacity. Material properties, insulation, surrounding temperature, methods of installation and grouping can change applicable current limits. The AWG wire gauge chart is a geometry reference, not an ampacity chart.

A resistance calculation also addresses a different question. For example, comparing two ideal conductors at equal material and length can illustrate the inverse relationship between resistance and cross-sectional area. It cannot establish either conductor's safe current. The wire area calculator deliberately provides only that mathematical relationship.

Voltage drop is a separate consideration

Even when a conductor's published reference ampacity is known, voltage loss depends on conductor impedance, length, current and the circuit model. The voltage drop calculator estimates that relationship from independently supplied impedance values. A voltage drop calculation does not establish a permissible conductor size, and an ampacity table does not determine the voltage drop of a particular circuit.

Check the original data before relying on a value

Review the exact product description, conductor construction, source revision and relevant footnotes. Requirements vary with the adopted edition and jurisdiction, and a manufacturer table may not contain every condition relevant to a specific installation. This limited reference is educational and does not establish suitability, compliance or safe operation. For practical decisions, use applicable standards, verified equipment specifications and qualified electrical review.

Source and additional learning

Source: Southwire SPEC 10003, Table 2 and its notes. The manufacturer does not endorse or certify ElecAtlas. See our calculation methodology, electrical reference library and electrical learning guides for related concepts.

Scope of the selector

Select one of the three sizes covered by the cited product data to compare the two published temperature columns. There is deliberately no load-current input, automatic gauge recommendation or pass/fail indicator. The reference does not cover every conductor size or material. When the exact product or operating conditions are unknown, a value from this example table cannot resolve the uncertainty; the source documentation and qualified review are needed.

The two temperature columns must be read together with the original product specification. A temperature value is not the ambient temperature or an instruction to operate a wire at that temperature. The published table is a reference to specific documented conditions.