Amps to kVA Calculator

Convert RMS current and voltage into apparent power in kVA for single-phase and balanced three-phase AC. Compare formulas and common input examples.

CALCULATOR WORKSPACE Live calculation
Calculated result—

Find apparent power from current and voltage

When the given quantities are RMS voltage and RMS current, apparent power is their product for a single-phase circuit. Divide volt-amperes by 1,000 to obtain kVA. For a balanced three-phase circuit, multiply line current and line-to-line RMS voltage by the square root of three before dividing by 1,000. The calculator uses total apparent power across the phases.

Formula and worked examples

For single-phase AC, S (kVA) = V × I / 1,000. For balanced three-phase AC, S (kVA) = √3 × VLL × I / 1,000. A 10 A RMS current at 120 V RMS corresponds to 1.2 kVA in the single-phase model. A 10 A line current at 400 V line-to-line corresponds to about 6.928 kVA in the balanced three-phase model.

Current conversion table

Each row is an illustrative mathematical operating point; the columns are not equipment ratings.

RMS current 120 V single-phase 240 V single-phase 400 V balanced 3-phase 480 V balanced 3-phase
1 A 0.120 0.240 0.693 0.831
2 A 0.240 0.480 1.386 1.663
5 A 0.600 1.200 3.464 4.157
10 A 1.200 2.400 6.928 8.314
15 A 1.800 3.600 10.392 12.471
20 A 2.400 4.800 13.856 16.628
25 A 3.000 6.000 17.321 20.785
50 A 6.000 12.000 34.641 41.569
100 A 12.000 24.000 69.282 83.138

All result columns are expressed in kVA. At a fixed voltage and circuit type, doubling the current doubles apparent power. The three-phase columns assume balanced loads and line-to-line voltage. A phase-to-neutral voltage is not interchangeable with the line-to-line value in this equation.

Is power factor needed?

No, not when converting RMS current and RMS voltage to apparent power in the specified model. Power factor becomes relevant when estimating real power from apparent power. A 5 kVA load at PF 0.8 has 4 kW of real power. At PF 0.6, its real power is 3 kW even though the apparent power is unchanged. Use kVA to kW for that conversion.

A reading of 20 A by itself does not identify a kVA value, because the voltage and circuit configuration are also needed. Likewise, the real power in watts cannot be obtained from kVA unless the relevant power factor is known. If you have measured real electrical input power rather than current, select a different converter.

Which inputs should I use?

Enter RMS values from the same operating condition. For balanced three-phase use line current, not the sum of the three currents. The voltage field refers to line-to-line RMS voltage in that mode. The calculated apparent power is not necessarily the rating of a generator, transformer or other supply. Equipment ratings may include thermal, loading and other constraints beyond these arithmetic relationships.

Reverse and check the conversion

Use kVA to amps with the same voltage and circuit type. For instance, 6.928203 kVA at 400 V in the balanced model gives approximately 10 A. If you need real electrical power directly from measured current, use amps to watts or amps to kW. For a conceptual introduction to RMS and power factor, read DC vs AC.

Limits and reference

This calculator assumes a single-phase or balanced three-phase model and nonnegative finite magnitudes. It does not analyze unbalanced loads, faults, wiring requirements, installation safety or equipment selection. The relationship between voltage and current must come from a known operating point. Results are rounded for display. Consult equipment documentation, the applicable standards and qualified professionals for actual installations. See electrical formulas and calculation methodology.

Check volts, amps and kilo-units

A result of 0.72 kVA corresponds to 720 VA, not 720 W unless power factor is one. If your instrument reports milliamps, divide by 1,000 to enter amperes. For example, 500 mA at a hypothetical 24 V RMS single-phase operating point corresponds to 0.012 kVA. Use measurements from the same load condition; a nominal supply voltage paired with an unrelated current reading may not describe a real operating point.