Battery Capacity Calculator

Estimate nominal battery capacity in watt-hours and amp-hours from load power, target runtime, voltage, usable energy and conversion efficiency.

CALCULATOR WORKSPACE Live calculation
Calculated result—

Nominal Wh = W × hours / usable fraction / efficiency

Estimate required nominal energy

Multiply average load power by the target runtime to obtain delivered energy. Divide by the assumed usable fraction and conversion efficiency to estimate nominal stored energy. Divide nominal Wh by nominal battery voltage to estimate Ah.

Example

A 60 W load running for eight hours needs 480 Wh delivered energy. At 80% usable energy and 90% efficiency, nominal capacity is approximately 666.67 Wh. At 12 V this corresponds to 55.56 Ah.

Capacity is not a complete system specification

The calculation is an energy budget only. It does not select a battery chemistry, charger, inverter, wiring or protective device. The required discharge current, starting surges, temperature range, battery management system, cutoff behavior and manufacturer limits must be assessed separately. Use values supplied by the manufacturer; the default usable fraction and efficiency are examples, not safety recommendations.

For varying loads, sum the energy needed over each operating interval before estimating storage. A device drawing 100 W for two hours and 25 W for four hours consumes 300 Wh in total.

Related tools

Battery runtime · mAh to Wh · Wh to mAh.

Compare nominal capacity with delivered energy

Consider a steady 40 W load for 5 hours. It needs 200 Wh at the load. If 80% of nominal energy is usable and the conversion efficiency is 90%, the estimated nominal energy is 277.78 Wh. At a nominal 24 V, that is about 11.57 Ah. These assumed percentages are illustrative, not battery specifications or recommended discharge limits.

Check the estimate against a known battery

After entering a candidate battery's rated Wh, use the battery runtime calculator to reverse the calculation. If a label gives mAh, use mAh to Wh and the nominal voltage associated with that rating. A battery with enough nominal energy may still be unable to supply the required current. Use the manufacturer's rated usable energy, operating limits and discharge curves where available; this tool does not verify compatibility or safety.

Compare required nominal energy for different runtimes

The table uses a hypothetical constant 60 W average load and two sets of illustrative usable-energy and conversion-efficiency assumptions. It describes an energy budget, not a battery product rating or recommendation.

Target duration Delivered energy Nominal Wh (u 80%, η 90%) Nominal Wh (u 90%, η 85%)
0.5 h 30 Wh 41.667 39.216
1 h 60 Wh 83.333 78.431
2 h 120 Wh 166.67 156.86
3 h 180 Wh 250 235.29
4 h 240 Wh 333.33 313.73
5 h 300 Wh 416.67 392.16
6 h 360 Wh 500 470.59
8 h 480 Wh 666.67 627.45
10 h 600 Wh 833.33 784.31
12 h 720 Wh 1000 941.18
16 h 960 Wh 1333.3 1254.9
24 h 1440 Wh 2000 1882.4

For the same load and assumed fractions, doubling target duration doubles nominal energy. Lower usable energy or lower conversion efficiency increases the nominal-energy estimate because more nominal stored energy is needed to deliver the same amount to the load.

Break a variable load into intervals

A single average-power input represents the entire intended operating period. For a hypothetical eight-hour schedule with 30 W for six hours and 90 W for two hours, delivered energy is 180 + 180 = 360 Wh. Average power is 45 W over eight hours. With illustrative usable fraction 0.8 and efficiency 0.9, the nominal estimate is 500 Wh. If efficiency differs between operating modes, a single average efficiency is only an approximation.

The estimate assumes the supplied usable-energy fraction and efficiency describe independent losses. If a manufacturer already states measured usable energy at a specified output, do not automatically subtract another identical loss. Identify what each rating actually measures before combining them.

Nominal Wh and equivalent Ah

Watt-hours represent energy; amp-hours represent charge. The simplified nominal relationship divides Wh by the associated nominal pack voltage. An illustrative 480 Wh energy rating corresponds to 40 Ah at 12 V or 20 Ah at 24 V. These examples compare nominal energy and charge, not interchangeable battery configurations. Actual compatibility and pack construction must be determined independently.

For a battery label in milliamp-hours, use mAh to Wh. For the inverse conversion, use Wh to mAh. Voltage associated with the nominal energy rating is the relevant quantity, not an unrelated charger or output connector voltage.

Account for what an energy model omits

Energy capacity alone does not identify permitted discharge current, peak power, temperature limits, cutoff behavior or system compatibility. An energy budget can be mathematically sufficient while the actual product cannot deliver the required current. Battery chemistry and condition also affect usable energy. The tool does not size protection, chargers or inverters.

Check the estimate in the other direction

For 500 Wh nominal energy, usable fraction 0.8 and conversion efficiency 0.9, estimated delivered energy is 360 Wh. Dividing by the example 45 W average load returns eight hours. Enter the same assumptions in the battery runtime calculator to cross-check the arithmetic. A change in real operating conditions invalidates that comparison.

Frequently asked questions

Does this select a safe battery for my appliance?

No. It estimates energy capacity only; equipment ratings and installation requirements need separate verification.